Siemens S7-400 CPU 414-4 H

6ES7 414-4HJ00-0AB0
V3.1
Fault-tolerant and failsafe capability, work memory 384 KB code and 384 KB data; 0.1 ms/1000 instructions; 8 KB
DI/O; 32 connections; 2*DP/MPI and 2 slots for H-Sync submodules; routing, firmware V3.1

Siemens S7-400 CPU 417-4 H

6ES7 417-4HL01-0AB0
V3.1
Fault-tolerant and failsafe capability, work memory 2 MB code and 2 MB data; (expandable to 20 MB); 0.1 ms/1000
instructions; 16KB DI/O; 64 connections; 2*DP/MPI and 2 slots for H-Sync submodules, routing, firmware V3.1

Siemens S7-400 CPU 417-4

6ES7 417-4XL00-0AB0
V3.1
Work memory 2 MB code and 2 MB data (expandable to 20 MB); 0.1 ms/1000 instructions; 16KB DI/O; 64
connections; 2*DP/MPI and 2 slots for IF submodules; with multicomputing capability, send and receive capability for
direct data exchange, constant bus cycle time and clocking, routing, firmware V3.1

Siemens S7-400 CPU 416-2 DP

6ES7 416-2XK02-0AB0
V3.1
Work memory 0.8 MB code and 0.8 MB data; 0.08 ms/1000 instructions; 16 KB DI/O; 64 connections; 2*DP/MPI;
send and receive capability for direct data exchange; constant bus cycle time and clocking; routing; with
multicomputing capability; firmware V3.1

Siemens S7-400 CPU 416F-2

6ES7 416-2FK02-0AB0
V3.1
work memory 0.8MB Code and 0.8MB data; 0.08 ms/1000 instructions; 16KB DI/O; 64 connections; 2*DP/MPI; send
and receive capability for direct data exchange; constant bus cycle time and clocking; routing; with multicomputing
capability firmware V3.1; can be used for security applications

Siemens S7-400 CPU 416-3 DP

6ES7 416-3XL00-0AB0
V3.1
Work memory 1,6MB code and 1,6MB data; 0.08 ms/1000 instructions; 16 KB DI/O; 64 connections; 2*DP/MPI and 1
slot for IF submodule; send and receive capability for direct data exchange; constant bus cycle time and clocking;
routing; with multicomputing capability; firmware V3.1

Siemens S7-400 CPU 414-3 DP

6ES7 414-3XJ00-0AB0
V3.1
Work memory 384KB code and 384 KB data; 0.1 ms/1000 instructions; 8 KB DI/O; 32 connections; 2*DP/MPI and 1
slot for IF submodule; send and receive capability for direct data exchange; constant bus cycle time and clocking;
routing; with multicomputing capability; firmware V3.1

Siemens S7-400 CPU 414-2 DP

6ES7 414-2XG03-0AB0
V3.1
Work memory 128KB code and 128 KB data; 0.1 ms/1000 instructions; 8 KB DI/O; 32 connections; 2*DP/MPI; send
and receive capability for direct data exchange; constant bus cycle time and clocking; routing; with multicomputing
capability; firmware V3.1

Siemens S7-400 CPU 412-2 DP

6ES7 412-2XG00-0AB0
V3.1
Work memory 72KB code and 72 KB data; 0.2 ms/1000 instructions; 2 KB DI/O; 16 connections; 2*DP/MPI; send and
receive capability for direct data exchange; constant bus cycle time and clocking; routing; with multicomputing
capability; firmware V3.1

Siemens S7-400 CPU 412-1

6ES7 412-1XF03-0AB0
V3.1
Work memory 48 KB code and 48 KB data; 0.2 ms/1000 instructions; 2 KB DI/O; 16 connections; 1*DP/MPI; send and
receive capability for direct data exchange; constant bus cycle time and clocking; routing; with multicomputing
capability; firmware V3.1

Memory Reset In Siemens PlC

Memory Reset

The CPU memory can be reset in STOP mode. The memory can be reset manually using the key switch (MRES) or from the programming device (for example, before downloading a user program).

Keep the Toggle key in the MRES for approximately 5 sec and then leave the switch.  Now the Memory reset is carried out

Resetting the CPU memory returns the CPU to its initial status, as follows:

The entire user program in the work memory and in the RAM load memory and all address areas are cleared.

The system parameters and the CPU and module parameters are reset to the default settings. The MPI parameters set prior to the memory reset are retained.

If a memory card (Flash EPROM) is plugged in, the CPU copies the user program from the memory card to the work memory (including the CPU and module parameters if the appropriate configuration data are also on the memory card).

The diagnostic buffer, the MPI parameters, the time, and the runtime meters are not reset


Configuration of a New module In Siemens PLC

Open Simatic Manager
Open the existing hardware configuration.
In the right side window you will find the available modules.
Select the required one to be added.
Click and drag the green slot in the left side of the configuration table.
Double click on the newly inserted module
Select the address manually/system selection.
Now save and compile
Then download to the PLC.
The configuration is complete

Slaves fault Diagnosis In Siemens PLC

Open the “Hard ware configuration” using  Simatic Manager .
Go to Station > Open Online.
Now the same configuration is opened in ONLINE mode.
See the next slide.
If there is any fault there will be a Red Mark on the CPU.
If you see the slave modules you will find a red slanting line over the slave.
Double click on that slave.
Go to Diagnosis .
Follow the steps of corrective action as mentioned.

PLC stop mode fault diagnosis In Siemens

Follow the procedure if the PLC is in stop mode.
Open the “Hard ware configuration” using  Simatic Manager .
Go to Station > Open Online.
Now the same configuration is opened in ONLINE mode.
If there is any fault there will be a Red Mark on the CPU.
Double click on that.
Go to Diagnosis.
There you will find the History of faulty before PLC went to stop mode.
Take corrective action as mentioned there.

By-passing In Siemens PLC

Follow the same procedure for “Modifying”
Force bit for ‘1’ is M 1.1 OR M 99.1
Force bit for’0’ is M 0.0 OR M 99.0.
Use any one of the relevant bits by following the procedure mentioned in the previous slide “Modifying the program”

Modifying the programm in siemens PLC

Open the particular block to be modified
Place the cursor where you want to insert the NO/NC contacts.
Click on the relevant icons for branches, NO, NC. 
Press :Enter”
Then download the block using PLC>Down load from the Simatic Manager Menu.


How To Downloading Programming Block In Siemens PLC

Downloading
Put the PLC in “STOP” mode
Establish the “ONLINE” connection between CPU and the PG
You can select the loadable objects in the project window and download them from the SIMATIC Manager (menu command: PLC > Download).
When programming blocks and when configuring hardware and networks you can directly download the object you were currently editing using the menu in the main window of the application you are working with (menu command: PLC > Download). 

How To UPLOADING Programm In Siemens PLC

Uploading Blocks to the Corresponding Project on the Programming Device
1.In the SIMATIC Manager, open the online window of the project using the menu command View > Online.
2.In the online window, select the block folder or a selection of the blocks in the folder.
3.Select the menu command PLC > Upload.
The selected objects are transferred to the project database on the programming device. 
UPLOADING COMPLETE BLOCKS TO A NEW FILE
Open Simatic manager.
Go to File>New
Give a new file name.
Now  from the Menu PLC>Upload station you can upload the station
The following steps are self explanatory
1. Select New File.
2.Name A New Upload file.
3. Select PLC - Upload Station.

4. Click On View.


5.Click On Ok Button.
 

STEP 7 BASICS TRAINING MODULE